Load voltage decay operation (open transition)
Load voltage decay utilizes the load voltage measurements to sense
back EMF that is generated when the transfer switch is in the
neutral position (electrical load disconnected). It provides a delay
in transfer in either direction if an unacceptable level is sensed
as established by a customer programmed level. The transfer will
not take place until the back EMF decays below the acceptable
programmed level. This feature has a separate setting of enabling or
disabling the operation. If disabled, the transfer switch will not delay
in the neutral position and will transfer between the sources as fast
as possible.