Time delay neutral operation (open transition)
Time delay neutral provides a time delay in the transfer switch
neutral position when both breakers/contactors are open. This delay
takes place when the load is transferred in either direction to prevent
excessive in-rush currents due to out of phase switching of large
motor loads.
Optional feature 29G: Type of operation (selectable automatic or
non-automatic)
This feature provides two door mounted selector switches marked
auto/manual and S1-trip-S2 which permits the selection of automatic
or manual operation. In manual operation, the user can manually initi
ate and electrically operate between S1. trip, or S2. On the contactor
bypass’s, 29G uses the top switch and the bottom switch. The newer
contactor bypasses (some starting in 2018) have 29G integrated and
standard for either the ATS or the bypass contactors. See the switch
instruction booklet for operating instructions. The controller is in
monitor mode during the manual operation meaning the controller
will not attempt to change the switch position but will monitor the
voltage availability and the switch positions. The ATC-900’s display
will show “Monitor Mode”.