Compatible with previous versions of
DeltaV systems
Switches are compatible with existing systems that are
installed using only our supported Cisco or Hirschmann
switches. Fiber communications of the Smart Switch will
only communicate at 100/1000MB full duplex (not
configurable) and wired ports will only auto-negotiate
communications (setting is not user adjustable).
Existing switches must be configured to run either in auto
negotiate mode or 100/1000MB full duplex communications.
Existing 3COM switches and media converters may not be
compatible with the DeltaV Smart Switch as they may not
support the required communications. The Smart Switch
will not plug and play in some older networks unless the
existing devices are set to match the specifications above
during the installation.
The auto switch lockdown is compatible only with DeltaV v10.3
and later revisions.
Please read DeltaV Books-on-line for important information
when retrofiting into existing DeltaV networks, especially in
systems with existing 3COM switches or media converters.
Fiberoptic connections on DeltaV Smart Switches are non
configurable and communicate only at 100Mbps on the DeltaV
ACN or 1Gbps switch-to-switch at full duplex.
Installing DeltaV Smart Switches into systems with existing
fiberoptic devices that are not set to 100/1000Mbps full duplex
will cause communications disruptions in the network.
Leave a comment