The S-series traditional I/O subsystem includes:
• I/O interface carrier (DIN-rail surface mounted) on which
all I/O related components are installed.
• Bulk AC to 24V DC power supply for field devices.
• A variety of analog and discrete I/O interfaces, consisting
each of an I/O card enclosed in a common form factor and
an associated I/O terminal block, which easily plug into the
I/O interface carrier.
• Cable extenders that provide flexibility in carrier mounting.
The I/O cards are connected to the field with a terminal block,
which allows removal of I/O cards without disconnecting any
field wiring.
DeltaV DCS provides control module level time stamping for log
events and alarms. For greater event resolution the 16-channel
Sequence of Event DI card can provide signal driven events to a
resolution of +/- 0.25 ms per card, or within 1 ms per controller.
Please refer to the Sequence of Events PDS for more information
on Sequence-of-event data collection and system options for this feature.