Product Description
This section provides general information on DeltaV SIS hardware. Refer to the Installing
Your DeltaV Distributed Control System manual for more information on DeltaV system hardware.
DeltaV SIS Hardware
The DeltaV SIS process safety system consists of the following hardware:
• Redundant Logic Solvers (SLS 1508) and termination blocks
• SISNet Repeaters (see separate product data sheet)
• Carrier extender cables
• Local peer bus extender cables
• Right 1-wide carrier with termination
Logic Solvers (SLS 1508) contain the logic-solving capability and provide an interface
to 16 I/O channels that can be configured as Discrete Input, Discrete Output, Analog Input
(HART) and HART two-state output channels. Logic Solversand termination blocks
install on the 8-wide carrier.
Logic Solvers communicate with each other through thecarriers over a two-channel,
local peer bus (SISnet) and remotepeer ring. Local Logic Solvers are hosted by the same DeltaV
controller and remote Logic Solvers are hosted by a different DeltaV controller.
Logic Solvers are powered by a 24 V DC power supply that is separate from the
power supply that drives the DeltaV controller and I/O. Logic Solvers install
in odd-numbered slots (1.3.5.7) on the 8-wide carrier.