Measured Variable Units and Ranges

Follow the prompts on the handheld communicator to define the following measured variables

units and ranges:

• Analog In Units – Permits defining the Analog Input Units in mA or percent of

4 to 20 mA range.

• Input Range Hi – Permits setting the Input Range High value. Input Range High should

correspond to Travel Range High, if the Zero Control Signal is configured as closed. If the

Zero Control Signal is configured as open, Input Range High corresponds to Travel Range

Low. See Figure 1.

• Input Range Lo – Permits setting the Input Range Low value. Input Range Low should

correspond to Travel Range Low if the Zero Control Signal is configured as closed. If the

Zero Control Signal is configured as open Input Range Low corresponds to Travel Range

High. See Figure 1.

• Pressure Units – Defines the output and supply pressure units in either psi, bar or kPa.

• LUI Pressure Units – Enter the pressure units displayed on the local user interface; psi, bar

or kPa.

• Temp Units – Degrees Fahrenheit or Celsius. The temperature measured is from a sensor

mounted on the digital valve controller’s printed wiring board.