Module Features
• Supports eight client connection to the RX3i Controller data set specified
in the configuration. [RBE supported only on one Client connection
associated with a specified port -Refer to GFK-2949B for details]
• Supports Interrogation and RBE for Single Point and Double Point data.
• Supports Interrogation and RBE for Regulated Step.
• Supports Interrogation and Measured data sets for Scaled, normalized,
and single precision Float.
• Supports 56-bit IEC 60870-5-104 time format, with the default being
56-bit time format.
• Supports Time Set, and query of the RX3i Controller CPU Clock in UTC time.
• Cause of Transmission size is two octets.
RX3i Interface specifications:
• Up to four EIS001 per RX3i, as allowed by available power and slots.
• Module can be installed in any available RX3i main rack I/O slot.
• Module supports insertion into and removal from an RX3i backplane
which is under power.
• Firmware upgrade through RX3i CPU using WinLoader software utility.