Module Features

• Supports eight client connection to the RX3i Controller data set specified

in the configuration. [RBE supported only on one Client connection

associated with a specified port -Refer to GFK-2949B for details]

• Supports Interrogation and RBE for Single Point and Double Point data.

• Supports Interrogation and RBE for Regulated Step.

• Supports Interrogation and Measured data sets for Scaled, normalized,

and single precision Float.

• Supports 56-bit IEC 60870-5-104 time format, with the default being

56-bit time format.

• Supports Time Set, and query of the RX3i Controller CPU Clock in UTC time.

• Cause of Transmission size is two octets.

RX3i Interface specifications:

• Up to four EIS001 per RX3i, as allowed by available power and slots.

• Module can be installed in any available RX3i main rack I/O slot.

• Module supports insertion into and removal from an RX3i backplane

which is under power.

• Firmware upgrade through RX3i CPU using WinLoader software utility.