DeltaV Licensing Guidelines
DeltaV I/O licensing for the VIM2 depends on the I/O cards
the VIM is emulating and follows that card type’s rules.
Programmable Serial Interface Cards
Serial dataset registers can be referenced directly in control
modules as analog or discrete I/O providing fast easy data
exchange with the serial device. Direct module-to-Dataset/
register references are recommended for control signals.
Alternatively, users can read multiple registers from a
Dataset into a single “marshalling” module at the cost of a
single DST. Marshalling modules provide a cost-effective
way to integrate serial data from analyzers and other data
sources. Serial dataset registers can also be passed as
SCADA values directly to Workstations and Continuous
Historians without consuming DST’s.
See the M-series Serial Interface Series 2 product data
sheet for additional details.