Ethernet I/O Integration
When used with the Ethernet I/O drivers, the VIM2
can communicate with high-speed Ethernet networks
over Modbus TCP, EtherNet/IP, FMC722. or PROFINET.
Depending on redundancy configuration of the VIM2. the
DeltaV controller auto-senses a commissioned VIM2 as four
or eight DeltaV I/O Cards.
• In simplex installations these cards will be sensed in slots 57-60 or 61-64.
• In dual simplex installations these cards will be sensed in slots 57 to 64.
• In redundant installations the redundant pairs will be sensed in slots 57 to 64.
Users configure the I/O signals for commissioned VIM2s
in DeltaV Explorer in the same manner as a DeltaV Serial, DeviceNet, or Profibus Card.