200 SERIES BASEPLATE MODULE MOUNTING

The 200 Series Fieldbus Modules mount on

200 Series baseplates which have been specially

designed to support them (see Figure 1. only vertical

baseplates shown – also FBMs do not mount on the

FCP270-only, FCM-only, or FBI-only baseplates).

The baseplates shown in Figure 1 fasten to a

structurally supported non isolated DIN rail for

mounting inside or outside an enclosure. (As an

alternative to DIN rail mounting, a mounting plate can

be used for horizontal mounting of the 200 Series

baseplate on a 19-inch rack). These baseplates can

thus be mounted in small, distributed cabinets or in a

variety of other mounting configurations.

ENCLOSURES

Enclosures extend the design of the 200 Series

FBMs by providing a range of mounting options to

match application requirements.

Figure 2. Dual or Redundant ISTA-*BP*

The G-Series enclosures are floor-standing units

which accommodate 200 Series baseplates for

mounting FBMs, FEMs, FCMs, and CPs, and/or

termination assemblies or terminal blocks for

marshalling. Most are available for use in ordinary

(IP 43/54) or harsh (IP 55/65) rated environments.

Several product lines of metal enclosures are offered

with the standard 200 Series subsystem:

 G-Series 800×800 Front and Rear Access

Enclosures (G10 system enclosure,

G11 termination enclosure, G12 system and

termination enclosure)

 G-Series 800×600 Front and Rear Access

Enclosures (G20 system enclosure,

G21 termination enclosure, G22 system and

termination enclosure)

 G-Series 800×800 Front-Only Access Enclosures

(G15 system enclosure, G16 termination

enclosure, G17 system and termination

enclosure)