The G60 Tricon System Enclosure provides environmental

protection and housing for Triconex™ Tricon system chassis

and modules.

FEATURES

The G60 Tricon system enclosure offers the following features:

• Accommodates up to three Tricon system chassis

• Main power entry includes disconnect terminal

blocks for 120/240 V ac or 125 V dc systems, or

10 A, Type D, double pole circuit breakers for

120/240 Vac systems.

• Optional EMC/RFI line filters for redundant main

power (Triconex recommended).

• Vented enclosure for use in ordinary (IP 43) rated

environments

• Option for EMC compliance

• Compact design to minimize use of floor space

with both front and rear access that allows

maximum density of enclosures in a control room

environment

• Options for front and rear access or front access

only, both with optional safety glass front door

• Optional door intrusion monitoring

• Alarm contact terminal block assembly for main

chassis alarming, door intrusion monitoring

switches, enclosure temperature switch and field

power supply status.

• Bottom cable entry for power wiring and cables

for Triconex termination devices, such as External

• Termination Panels (ETPs), Field Terminations and

• External Termination Assemblies (ETAs)

• Conveniently placed eyebolts for transporting

and lifting the enclosures

• A 100 mm (4 in) plinth – total enclosure height of

2160 mm (85.0 in)

• Comfort handles with push-button/keylocks

Three earth (ground) points; two protective earth

(ground) studs, one isolated protective earth

(ground) rail and one isolated instrument earth

(ground) rail.