Motor Thermal Model
The M60 features an enhanced motor
thermal model consisting of the following
elements:
• Thermal limit curves – NEMA standard,
voltage dependent and customized
• IEC 60255-8 thermal overload curves
• Current unbalance biasing
• Independent running and stopped
exponential cooling curves
• Optional RTD biasing of the thermal
model to adapt to real-time
temperature measurements
• Compensation for hot/cold motor
conditions
The M60 thermal model integrates both
stator and rotor heating and cooling into
a single model.
FlexCurves™
For applications that require greater
flexibility, FlexCurves can be used to define
custom curve shapes. These curves can
be used to protect motors with different
rotor and stator damage curves, allowing
complete protection over the total motor
capacity.
Leave a comment