Reaction in the Event of a Fault
If the device detects a fault on a digital input, the user program processes a low level in
accordance with the de-energized to trip principle.
The device activates the FAULT LED.
In addition to the channel signal value, the user program must also consider the
corresponding error code.
The error code allows the user to configure additional fault reactions in the user program.
Safety-Related Digital Outputs
The controller is equipped with 8 digital outputs. The state (HIGH, LOW) of each output is
signaled by an individual LED.
At the maximum ambient temperature, each of the outputs 1…3 and 5…7 can be loaded
with 0.5 A, and outputs 4 and 8 can be loaded with 1 A or 2 A at an ambient temperature of
up to 50 °C.