Safety Function
No safety function is performed by the communication module.
Reaction in the Event of a Fault
If fault occur, the module enters the temporary ERROR STOP. The module is then rebooted
and restarted from the INIT state.
No process data is exchanged with external communication partners in the ERROR STOP
state. No process data is transferred to process module.
HIMax COM Module Part Number
Each COM module forms a functional unit with the X-CB 001 02 connector board. Note that the
connector board must be separately purchased.
The fieldbus submodules are optional and must be mounted by the manufacturer. The fieldbus
submodule is selected when ordering the controller using the part number. Additionally, the
protocols used must be activated.
Processor System
The processor system uses self tests to control and monitor the communication.
Data is exchanged between the communication module and the processor module
is carried out via redundant system bus. The system bus has a redundant structure
for reasons of availability. Redundancy is only ensured if both system bus modules
are inserted in the base plates and configured accordingly.
Operating system and error code history are stored in a non-volatile memory and
can be read in SILworX via the diagnosis.