560CVD03 Multimeter, 1A/5A, 3U3I
CT/VT Interface with 3 Voltage and 3 Current Inputs for Direct Monitoring of 3-Wire 85…. .400 VAC
1/5 A input for AC transformer
RTU500 serial interface (RS-485)
APPLICATIONS
The multimeter 560CVD03 is used to monitor input signals from three independently phased 3-wire or 4-wire connections.
Voltage, current and power can be measured directly for each phase and a number of other parameters can be derived via software. The measurement results www.cniacs.com are transmitted to the RTU560.
Several versions are available:
Power measurement display
It automatically switches the screens of the measurement page and displays each screen for 6 seconds.
Six seconds.
If changed to key mode, each screen will automatically display 240 seconds. Scroll mode can be set with the RTUtil560.
Features
Multimeters are microprocessor-based Intelligent Electronic Devices (IEDs) used to measure current, voltage, power, and energy.
Derived parameters are calculated once in 500 milliseconds and then scaled according to user-programmed constants for current and voltage transformers.
The current and voltage inputs of the 560CVD03 are connected only through the appropriate transformers (see Figures 3 and 4).
The multimeter can be mounted on a 35 mm DIN rail.
Meter Operation
The following metering parameters are available
Instantaneous Meter Value
Measured by true RMS conversion and transmitted to the RTU560 with the following values