The Hydran M2-X is the next generation of the field-proven family of Hydran DGA monitoring solutions,

providing continuous monitoring of gas and moisture levels to alert users of developing faults and minimize the risk of unplanned outages.

The M2-X builds on GE’s strong domain expertise to deliver an optimized,

low maintenance monitoring device with extended sensor life.

The Hydran M2-X is also available in a UL certified, HazLoc version (part number: M2-X-HZ)

for installation on transformers located in hazardous locations designated as Class I, Division 2

The Hydran sensors are available as a traditional Hydran composite gas (H2. CO, C2H2. C2H4) sensor or a discrete Hydrogen only (H2) sensor.

In addition, it tracks moisture in oil (reading in %RH and ppm) and is compatible with various transformer oil types

(standard mineral insulating oils and newer natural and synthetic ester based fluids).

Features

Easily upgradeable in the field to accept analog signals and monitor other key transformer parameters

Computation of winding hot spot and other IEEE transformer models for enhanced diagnostics

of the transformer’s condition (depending on sensors installed)

Easy to install on a single existing transformer valve, often without an outage required

Integrated display and keypad for simplified local user interaction and data visualization

Built-in moisture sensor provides water in oil measurement, critical to identify paper degradation and leaking gaskets

Compatible with GE’s acclaimed Perception™ software to download, trend and analyse transformer health data