Configuration
The IC697 CPU and I/O system is configured with
MS-DOS or Windows based programming software.
There are no DIP switches or jumpers used to config
ure the system. The CPU verifies the actual module
and rack configuration at power-up and periodically
during operation. The actual configuration must be
the same as the programmed configuration. Devi
ations are reported to the CPU alarm processor func
tion for configured fault response. Consult Reference
1 for a description of configuration functions.
Batteries
A lithium battery (IC697ACC701) is installed as shown
in Figure 2. This battery maintains program and data
memory when power is removed and operates the
calendar clock. Be sure to install the new battery be
fore removing the old battery. If during power-up
diagnostics a low battery is detected the Module OK
LED (top) will not stay on. Specific indication of a low
battery state is detailed in Reference 2.
Removing a Module
The following instructions should be followed when
removing a module from its slot in a rack.
Grasp the board firmly at the top and bottom of
the board cover with your thumbs on the front of
the cover and your fingers on the plastic clips on
the back of the cover.
Squeeze the rack clips on the back of the cover
with your fingers to disengage the clip from the
rack rail and pull the board firmly to remove it
from the backplane connector.
Slide the board along the card guide and remove it
from the rack.