Electrically isolated IDNet 2 addressable initiating device SLC:

• Provides built-in short circuit isolation for monitoring and

control of TrueAlarm analog sensors and IDNet communications

monitoring and control devices. For use with either shielded or

unshielded, twisted or untwisted single pair wiring. Outputs are

Class A or Class B.

• Standard panel signaling line circuit (SLC) provides up to 100

addressable points. Optional additional loop expansion modules

provide an additional isolated loop with short circuit isolation for

the IDNet 2 channel. Each loop expansion module also provides

an additional 75 addressable points.

Power supply:

• Four notification appliance circuits (NACs), you can select as Class

A or Class B with 6 A total available current

• You can select the NAC EOL resistor value from a wide range of

resistance values for retrofit convenience

• For additional notification power capacity, use a 4009 IDNet NAC

Extender.

• Battery backup charging of up to 33 Ah. Up to 18 Ah for cabinet

mounted batteries and up to 33 Ah for batteries mounted close

nippled, in a remote battery cabinet.

General mechanical:

• Red or platinum cabinet. Rated NEMA 1 and IP30.

4007ES Listings reference:

• UL 864 – Control Units, System (UOJZ). Control Unit Accessories,

System, Fire Alarm (UOXX). Control Units, Releasing Device Service

(SYZV)

• UL 2017 – Emergency Alarm System Control Units (CO detection),

(FSZI)

• ULC-S559 – Central Station Fire Alarm System Units (DAYRC)

• ULC-S527 – Control Units, System, Fire Alarm (UOJZC). Control Unit

Accessories, System, Fire Alarm (UOXXC). Control Units, Releasing

Device Service (SYZVC)