Software feature summary:

• Current and previous panel configuration is maintained in on

board memory

• An internal Ethernet service port is available for service computer

connections to perform configuration updates, downloads and

uploads, report downloads, and update system software

• You can use the internal USB interface with a memory stick to

store job revisions, update revised jobs and panel software, and

save detailed system reports from the panel.

Optional modules and connections include:

• Fire alarm network interface card (NIC) for ES Net or 4120 network

• Peer-to-peer network communications, supports either Class B or

Class X operation

• Point or Event DACT assembly for Connected Services Gateway

• Up to two additional IDNet 2 addressable device output loop

connections with short circuit fault protection and with 75

additional point capacity each.

• Front mounted 32 LED and 32 LED/switch annunciator with

custom label inserts. LEDs are programmable for up to 32

IDC zones of alarm and trouble annunciation or other custom

annunciation requirements.

• Remote LED annunciator support through remote user interface

(RUI) communications port for use with UTP wiring.

• Dual RS-232 ports for printer, PC annunciator, or third party interface.

• Alarm relays and auxiliary relays.

• City connections, with or without a disconnect switch.

• 4009 IDNet NAC Extenders to extend NAC capability for power and

distance

• Battery brackets for seismic area protection.