Operator interface

Convenient status information

If the locking door is closed, through the glass window, you can view

the display status of the LEDs. The user interface is a 4.3 in. (109

mm) diagonal color touchscreen LCD with separate status LEDs. See

Figure 2.

LED indicators describe the general category of activity displayed and

the LCD provides more detail. Authorized users can unlock the door

to gain access to the control functions and scroll through the display

for additional detail.

Operator interface and software features

• Convenient and detailed operator information is easily accessible

using a logical, menu-driven touchscreen display with password

access control

• Multiple automatic and manual diagnostics for maintenance

reduction

• Alarm and Trouble History Logs, up to 1000 entries for each, 2000

total events. You can view these events from the display or print

them out on connected printer, or download them to a service

computer.

• Module level ground fault searching assists installation and

service by locating and isolating modules with grounded wiring

• WALKTEST silent or audible system test performs an automatic

self-resetting test cycle and supports up to eight WALKTEST

groups

• Install Mode can group multiple troubles for uninstalled modules

and devices into a single trouble condition, typical with future

phased expansion. With future equipment and devices grouped

into a single trouble, operators can clearly identify events from

the commissioned and occupied areas.