Introduction
This document is designed to assist and guide a trained technician or engineer to diagnose and
troubleshoot the Smart Equipment Controller alarms. When troubleshooting always use Johnson
Controls and industry safety standards.
Preliminary checks
No power
The Smart Equipment™ Control (SEC) board requires 24 VAC to operate. If no power is provided then
no alarms are active, the LCD screen is blank, and the unit does not function at all.
1.on the upper left hand of the board using the voltmeter.–
If no voltage is present, check the wiring diagram and trace where the 24 VAC power is
lost.
If voltage is present and no power is indicated on the SEC board through the LCD
display or power LED indicator, replace the board.
2.Check for optional components such as the phase monitor in the circuit. If there is a red light
visible on the phase monitor, this indicates that the board is not receiving power. Swap the
incoming voltage going to the unit, not the voltage within the unit.