Applications
– Synchronous or induction generators operating at 25Hz, 50Hz or 60Hz
– Primary or backup protection in cogeneration applications
Protection and control
The 489 generator protection system provides comprehensive protection,
metering and monitoring functions for small and medium-sized synchronous or
induction generators operating at 25. 50 or 60 Hz.
The 489 is ideal for primary or standby generator protection as well as cogeneration applications.
The 489’s protection features include:
Generator stator differential
The 489 uses high speed dual slope differential protection to detect and clear stator phase faults.
Stator phase faults. Advanced CT saturation detection algorithms provide
additional supervision through the use of directional checks that
ensures that the fault occurs inside the generator before triggering a trip,
thus maintaining immunity to saturation that may be caused by external disturbances.
100% Stator Ground
100% stator ground fault protection is provided by an overvoltage element and an
adaptive differential voltage function that responds to third harmonic imbalances at the machine
terminals and neutral.
The 489 will compare the machine neutral voltage with the grounding
current to determine if the ground fault is internal or external to the generator.