provides 32 discrete input points that operate at levels up to 30V. Power to operate field
devices can come from an external supply or from the module’s isolated +24 VDC output.
48VDC 32 Point Positive/Negative Logic Input module, IC694MDL658. provides
32 discrete input points that operate at levels up to 60V. Power to operate field
devices must be provided using an external supply.
The blue band on the front label indicates a low-voltage module.
These modules do not report special fault or alarm diagnostics. Green LEDs
indicate the ON/OFF status of each input point.
These modules can be installed in any I/O slot in the RX3i system.
Installation in Hazardous Locations
• EQUIPMENT LABELED WITH REFERENCE TO CLASS I, GROUPS A, B, C & D, DIV. 2 HAZARDOUS
LOCATIONS IS SUITABLE FOR USE IN CLASS I, DIVISION 2. GROUPS A, B, C, D OR NON-HAZARDOUS
LOCATIONS ONLY
• WARNING – EXPLOSION HAZARD – SUBSTITUTION OF COMPONENTS MAY IMPAIR SUITABILITY FOR
CLASS I, DIVISION 2;
• WARNING – EXPLOSION HAZARD – WHEN IN HAZARDOUS LOCATIONS, TURN OFF POWER BEFORE
REPLACING OR WIRING MODULES; AND
• WARNING – EXPLOSION HAZARD – DO NOT DISCONNECT EQUIPMENT UNLESS POWER HAS BEEN
SWITCHED OFF OR THE AREA IS KNOWN TO BE NONHAZARDOUS.