F4T Base Specifications

Line Voltage/Power

• High voltage option: 100 to 240VAC +10/-15%, 50/60Hz ±5%

• Low voltage option: 24 to 28VAC/VDC+10/-15%, 50/60Hz ±5%

• Power consumption: 23 W, 54VA

Environment

• NEMA 4X/IP65 front panel mount configuration only

• Operating temperature: 0 to 122°F (-18 to 50°C)

• Storage temperature: -40 to 185°F (-40 to 85°C)

• Relative humidity: 0 to 90%, non-condensing

Agency Approvals

• UL®/EN 61010 Listed, File E185611 QUYX

• UL® 508 Reviewed

• CSA CC.C#14, File 158031

• FM Class 3545 (configurations with limit modules)

• AMS 2750 E compliant: Analog input process values. Tip: Maximize

field calibration accuracy and uniformity by using advanced F4T

features such as Calibration Offset and Linearization Function

Blocks. Refer to user manual for details.

• RoHS by design, China RoHS Level 2, W.E.E.E.

• CE

• Windows® Hardware Certification