High-amperage power control output (1/16 DIN only)

• Drives 15 ampere resistive loads direct

• Reduces component count

• Saves panel space and simplifies wiring

• Reduces cost of ownership

PM LEGACY™

Specifications

Line Voltage/Power

• 85 to 264VAC, 47 to 63Hz

• 20 to 28VAC, +10/-15%; 50/60Hz, ±5%

• 12 to 40VDC

• 10VA (1/32 and 1/16 DIN)

• Data retention upon power failure via non-volatile

memory

• Compliant SEMI F47-0200, Figure R1-1 voltage sag

requirements @ 24VAC or higher

Environment

• 0 to 149°F (-18 to 65°C) operating temperature

• -40 to 185°F (-40 to 85°C) storage temperature

• 0 to 90% RH, non-condensing

Accuracy

• Calibration accuracy and sensor conformity: ±0.1%

of span, ±1°C @ the calibrated ambient temperature

and rated line voltage

• Type S: 0.2%

• Type T below -50°C: 0.2%

• Calibration ambient temperature @ 77°F ±5°F

(25°C ±3°C)

• Accuracy span: 1000°F (540°C) min.

• Temperature stability: ±0.1°F/°F (±0.1°C/°C) rise in

ambient max.

Agency Approvals

• cULus® UL®/EN/CSA C22.2 No 61010-1 Listed,

File E185611

• CSA C22.2 No. 24, File 158031

• UL® 50 4X indoor locations, NEMA 4X, IP66,

IP67 front seal

• cULus® ANSI/ISA 12.12.01-2007, CSA-C22.2 No.

213-1987, Class 1, Div. 2, Groups A, B, C and D,

temperature code T4A, File E184390 (optional)

• CE, RoHS by design, W.E.E.E.

• FM Class 3545 (limit controls)