High-amperage power control output (1/16 DIN only)
• Drives 15 ampere resistive loads direct
• Reduces component count
• Saves panel space and simplifies wiring
• Reduces cost of ownership
PM LEGACY™
Specifications
Line Voltage/Power
• 85 to 264VAC, 47 to 63Hz
• 20 to 28VAC, +10/-15%; 50/60Hz, ±5%
• 12 to 40VDC
• 10VA (1/32 and 1/16 DIN)
• Data retention upon power failure via non-volatile
memory
• Compliant SEMI F47-0200, Figure R1-1 voltage sag
requirements @ 24VAC or higher
Environment
• 0 to 149°F (-18 to 65°C) operating temperature
• -40 to 185°F (-40 to 85°C) storage temperature
• 0 to 90% RH, non-condensing
Accuracy
• Calibration accuracy and sensor conformity: ±0.1%
of span, ±1°C @ the calibrated ambient temperature
and rated line voltage
• Type S: 0.2%
• Type T below -50°C: 0.2%
• Calibration ambient temperature @ 77°F ±5°F
(25°C ±3°C)
• Accuracy span: 1000°F (540°C) min.
• Temperature stability: ±0.1°F/°F (±0.1°C/°C) rise in
ambient max.
Agency Approvals
• cULus® UL®/EN/CSA C22.2 No 61010-1 Listed,
File E185611
• CSA C22.2 No. 24, File 158031
• UL® 50 4X indoor locations, NEMA 4X, IP66,
IP67 front seal
• cULus® ANSI/ISA 12.12.01-2007, CSA-C22.2 No.
213-1987, Class 1, Div. 2, Groups A, B, C and D,
temperature code T4A, File E184390 (optional)
• CE, RoHS by design, W.E.E.E.
• FM Class 3545 (limit controls)
Leave a comment