CLS200 Specifications
Operator Interface
• 32-character vacuum fluorescent display
• 8-key keypad to access guided menus and prompts,
enter passkey sequence, set values, switch between
single channel and multiple channel displays
• Controller configuration can be loaded through the
standard serial port
Analog Inputs
• CLS204 4 differential
• CLS208 8 differential
• CLS216 16 single-ended
Noise Rejection
• 120dB at 60Hz
Temperature Coefficient
• 40ppm/°C
Sensors/Inputs
• Thermocouples: user-selectable type, direct connection,
linearization, reference junction compensation, reversed
and shorted thermocouple detection and upscale break
protection with output averaging
• RTD: (CLS204 and CLS208 only) 2- or 3-wire, platinum,
100Ω @ 0°C, DIN 0.003850Ω/Ω/°C curve, user-selectable
range. Two user-selectable ranges offer different
resolutions. Requires scaling resistors. See special/linear
inputs in ordering information.
• Linear: current and voltage signals from linear transmitters
• Pulse input