□ FUNCTIONAL SPECIFICATIONS
Output “◊”
For 4 to 20 mA HART / BRAIN
(Output signal code D and J)
Two wire 4 to 20 mA DC output with digital
communications, linear or square root programmable.
BRAIN or HART FSK protocol are superimposed on
the 4 to 20 mA signal.
Output range: 3.6 mA to 21.6 mA
Output limits conforming to NAMUR NE43 can be
pre-set by option code C2 or C3.
For 1 to 5 V HART
(Output signal code Q)
Three or four wire low power 1 to 5 V DC output with
HART, linear or square root programmable.
HART protocol are superimposed on the 1 to 5 V DC
signal.
Output range: 0.9 V to 5.4 V DC
Failure Alarm
For 4 to 20 mA HART / BRAIN
(Output signal code D and J)
Analog output status at CPU failure and hardware
error;
Up-scale: 110%, 21.6 mA DC or more (standard)
Down-scale: −5%, 3.2 mA DC or less
For 1 to 5 V HART
(Output signal code Q)
Analog output status at CPU failure and hardware
error;
Up-scale: 110%, 5.4 V DC or more (standard)
Down-scale: −5%, 0.8 V DC or less
Damping Time Constant (1st order)
Amplifier damping time constant is adjustable from
0.00 to 100.00 s by software and added to response
time.
Note: For BRAIN protocol type, when amplifier software
damping is set to less than 0.5 s, communication
may occasionally be unavailble during the
operation, especially while output changes
dynamically. The default setting of damping
ensures stable communication.
Update Period “◊”
Differential pressure: 45 ms
Static pressure: 360 ms
Zero Adjustment Limits
Zero can be fully elevated or suppressed, within the
lower and upper range limits of the capsule.