Hardware Features
The thermocouple module fits into any single-slot, except the
processor slot (0), in either an SLC 500 modular system or an SLC 500
fixed system expansion chassis (1746-A2). It is a Class 1 module (uses
8 input words and 8 output words). It interfaces to thermocouple
types J, K, T, E, R, S, B, and N, and supports direct ±50 mV and ±100
mV analog input signals.
The module requires the use of Block Transfer in a remote configuration.
The module contains a removable terminal block providing
connection for four thermocouple and/or analog input devices. There
are also two, cold-junction compensation (CJC) sensors used to
compensate for offset voltages introduced into the input signal as a
result of the cold-junction, i.e., where the thermocouple wires connect
to the module wiring terminal. There are no output channels on the
module. Module configuration is done via the user program. There are
no DIP switches.