The DSLC-2 / MSLC-2 system can be applied according to following rules:

• The maximum number of DSLC-2s (Gen-CB) is 32.

• The maximum number of MSLC-2s (Utility- or Tie-CB) is 16.

• The maximum number of segments is 8.

• The segment numbers have to follow a line, which can finally be closed to a ring.

• For DSLC-2 it can be selected between two segmenting modes:

o Bus segmenting determining generators running together via an algorithm.

o Device segmenting determining generators running together from outside.

• Only one MSLC-2 can be used as master control, when multiple MSLC-2 is resided in one segment.

o The MSLC-2 with the lower device number will control if multiple Utility MSLC-2s are

active on the same segment

• The generator is not counted as a segment.

• The utility is not counted as a segment.