Valve Status (local & remote)

Each valve solenoid accepts power for one or two (redundant) power sources and has the following

status indications to assist operators with understanding the status and health of each valve.

• Valve Open—Local LED (red)

• Valve Open—Limit Switch

• Valve Closed—Local LED (green)

• Valve Closed—Limit Switch

• Power Supply #1 Healthy—Local LED (blue)

• Power Supply #2 Healthy—Local LED (blue)

Redundancy/Availability

Designed for use in critical gas and steam turbine applications where turbine up time is important, the

QuickTrip uses three isolated solenoid valves designed to be driven by a triple modular redundant 2-out

of-3 voting based safety logic solver. Each isolated solenoid valve uses redundant power supply inputs to

increase both system reliability and availability. Note: only one power source is required to

power/energize each of the isolated solenoid valves.

On-Line Repairable

The QuickTrip’s modular design allows independent repair/replacement of each valve’s solenoid,

electrical module, and associated power supplies and wiring to increase both system reliability and

availability. Note: only one power source is required to power/energize each of the isolated

solenoid valves.