Remove the top access cover(s). Pass the wires through the cable gland (not provided) or conduit fitting
and attach wires to the printed circuit board terminal blocks in accordance with the wiring diagram.
Secure each wire into connector terminal using a 2.5 mm flat screwdriver blade, applying a torque of
0.2-0.25 Nm (1.75-2.25 in-lbf). Snap the terminal blocks into the header terminal blocks on the PCB.
Tighten the terminal block flange screws to 0.5 Nm (4.4 in-lbf). Replace the top access cover and torque
it using a 1 meter bar or wrench; tightening until the O-ring seal is compressed and the cover is fully
seated against the housing.
Tighten the cable gland fitting per manufacturer’s instructions or pour the conduit seal to provide strain
relief for the cable and to seal the interface between the wiring cable and the QuickTrip modules.
In order to preserve the QuickTrip’s online reparability, each of the three electrical actuator cavities must
be kept isolated from each other. This allows any individual actuator requiring repair to be electrically de
energized, repaired and placed back online while maintaining safe operation of QuickTrip in potentially
explosive environments.
Leave a comment
Your email address will not be published. Required fields are marked *