The shield connections for the Analog Output (terminal #20), CAN1 (terminal

#23), and CAN2 (terminal #29) are through capacitors only as indicated in the

wiring section of this manual.

The power supply section performs the EMI filtering on the (18 to 32) V (dc) input

voltage and generates controlled voltages for several electronics sub-systems.

The power supply system is monitored for proper operation. If input voltage or

internal power systems are detected outside of allowable operating ranges, a

diagnostic alarm will be enunciated.

Calibration and configuration of alarms and shut down and redundancy operation

are configurable via the PC Service Tool.

The primary demand and redundant demand / feedback input signals are

designed for a (4 to 20) mA control signal. Each input signal is EMC protected.

Discrete outputs are provided for alarm and shut down enunciation. An internal

LED also is illuminated when a fault condition is detected. Cover needs to be

removed to see this LED. The configurable discrete output can be customized to

output a variety of enunciations using the PC Service Tool. All of the discrete

outputs are configurable for normally-open or normally-closed action using the

PC Service Tool.