Description
The GSOV50 fuel isolation valve provides shutdown on a gas turbine by rapidly
halting the flow of gaseous fuel. The supply pressure is used to move a spring
loaded piston in the valve. When the valve is energized, gas pressure drives the
spring-loaded piston open, admitting fuel to the turbine. When the current signal to
the electrical solenoid is interrupted, the spring loaded second-stage piston changes
states to vent off primary control pressure. The main spring then forces the primary
piston to the seal, stopping all flow.
Product Variants
• 24 VDC or 125 VDC Input Voltage Options
• Internal or External Pilot Pressure Options
• Proximity Switch with Normally Open or Closed Contacts
Product Specifications
• Gas Supply Pressure: 100-900 psig (690-6200 kPA)
• Fuel Temperature: -4 to +350 degrees Fahrenheit (-20 to +177 degrees Celsius)
• Ambient Temperature: -4 to +250 degrees Fahrenheit (-20 to +121 degrees Celsius)
• Main Seat Forward Leakage: ANSI/FCI 70-2. Class VI
• Main Seat Reverse Leakage: ANSI/FCI 70-2. Class VI, up to 500 psid (3.448kPA) reverse pressure
differential
• Flange: ANSI 600# RF Flange