Specifications
Inputs per Module: 8. 16 or 32
Classic
Isolation: 1500 VDC channel-to-backplane
1500 VDC group-to-group
Input Voltage:
Range Setting
12/24V range
48V range
110V range
220VAC range
Operating Range
11 – 30 volts
40 – 56 volts
79 – 132 volts
164 – 240 volts
*NOTE: 220V range is AC only
Input Current: AC: 2.1—3.6 mA
DC: 2.5—4.3 mA
Operating Characteristics for Typical Input:
AC Voltage Input:
Turn ON Time: 4.0mS
Turn OFF Time: 15.0mS
DC Voltage Input:
Turn ON Time: 1.0mS
Turn OFF Time: 15.0mS
Connector: 2500-40F Removable Connector (sold
separately)
Wire Gauge: 14-22 AWG
Backplane Power: 3.6 Watts max.
Module Size: Single-wide
Operating Temperature: 0° to 60°C
(32° to 140°F)
Storage Temperature: -40° to 85°C
(-40° to 185°F)
Relative Humidity: 5% to 95%
(non-condensing)
Shipping Weight: 1.5lb (0.68 Kg)
Voltage Range Selection Jumpers
The 2589-B will handle a wide range of AC and DC signals,
and has incorporated the ability to select either 12V/24V, 48V,
110V, or 220V on a per channel basis using jumper selection.
The selections are made individually for each of the 32
channels using jumpers. However, the same voltage range
must be selected for all channels in the same group. The
operating ranges are as follows:
Range Setting
12/24V range
48V range
110V range
220VAC range
Operating Range
11 – 30 volts
40 – 56 volts
79 – 132 volts
164 – 240 volts
* NOTE: 220V range is AC only