Welcome to the official website of CNIACS Automation Technology Co., Ltd!

CTI 2557-A Asynchronous Operation

Asynchronous Operation

The module operates asynchronously with respect to the PLC; a scan

of the PLC and input sampling of the module do not occur at the same

time. Instead, the module will translate all inputs in one module update

(20 milliseconds maximum) and store the translated words in a buffer

memory. The PLC retrieves the stored words from the module buffer

memory at the start of the I/O scan.

Compatibility with Immediate I/O

The Model 2557-A has been tested and is compatible with the

Immediate read function of the SIMATIC® 545 and 555 PLC.

100 Ohm, 10 Ohm, 120 Ohm RTDs, or Millivolt Inputs

Each of the module’s 16 channels may be configured to receive either

a 100 Ohm platinum RTD or a 120 Ohm nickel RTD or a 10 Ohm

copper RTD input signal (two, three or four wire) or a DC voltage signal

ranging from 0 to 100 millivolts. Selection of 10 Ohm, 100 Ohm or 120

Ohm RTDs or millivolts are made via internal switch and jumper settings.

CTI 2557-A 100 Ohm, 10 Ohm, 120 Ohm RTDs, or Millivolt Inputs

100 Ohm, 10 Ohm, 120 Ohm RTDs, or Millivolt Inputs

Each of the module’s 16 channels may be configured to receive either

a 100 Ohm platinum RTD or a 120 Ohm nickel RTD or a 10 Ohm

copper RTD input signal (two, three or four wire) or a DC voltage signal

ranging from 0 to 100 millivolts. Selection of 10 Ohm, 100 Ohm or 120

Ohm RTDs or millivolts are made via internal switch and jumper settings.

Digital Word Map

RTD and/or millivolt signals are translated into a 14-bit digital word.

Since the PLC requires a 16-bit input word, the 14-bit value from the

converter is placed into a 16-bit word for transmittal to the PLC.

As shown in the following figure, of the two bits not used for the digital

word, one is used to show the sign of the word, while the other is used

to note values which are “overrange or underrange.”

CTI Model 2556-A is designed to translate a J, K, R, S, T, E

The Model 2556-A is designed to translate a J, K, R, S, T, E, and L

(DIN J) thermocouple or millivolt input signal into an equivalent digital

word which is then sent to the programmable controller (PLC).

The 2556-A Thermocouple Input Module features built-in independent

internal cold junction compensation and linearization for each

thermocouple input for Types J, K, E, R, S, L, and T. No external cold

junction compensation is required.

FEATURES

• CTI 2500 Series® and Simatic® 505 I/O base format

• 1500V isolation channel-to-PLC backplane

• 1500V isolation channel-to-channel

• Supports J, K, R, S, T, E, and L thermocouples and millivolt inputs

• Advanced preprocessing with on-board scaling, alarm detection,

filtering and averaging jumper selectable function uses 16X/16Y/

32WX/32WY login

• Fast 20 mSec update time

CTI 2556-A 16-Channel Isolated Thermocouple Input Module

DESCRIPTION

The 2556-A is a high-speed 16-channel thermocouple input module

designed to be compatible with the CTI 2500 Series® and Simatic®

505 I/O base. The 2556-A translates millivolt level signals from the

thermocouple element into a scaled temperature value.

Multiple thermocouple types are supported as well as millivolt inputs.

Scaling, alarm detection, filtering, peak and valley hold, and averaging

are supported on a channel-by-channel basis. All parameters may

be loaded into the module directly with relay ladder logic.

The Sixteen Channel Thermocouple Input Module is a member of

Control Technology’s family of I/O modules compatible with the all

2500 Series 2500® Processors and the SIMATIC® 505 Series

programmable controllers.

CTI 2556 16-Channel Isolated Thermocouple Input Module

DESCRIPTION

The 2556 is a high-speed 16-channel

thermocouple input module designed to be

compatible with the CTI 2500 Series® and

Simatic® 505 I/O base. The 2556 translates

millivolt level signals from the thermocouple

element into a scaled temperature value.

Multiple thermocouple types are supported as

well as millivolt inputs. Scaling, alarm detection,

filtering, peak and valley hold, and averaging

are supported on a channel-by-channel basis.

All parameters may be loaded into the module

directly with relay ladder logic.

FEATURES

 CTI 2500 Series® and Simatic® 505 I/O base

format

 1500V isolation channel-to-PLC backplane

 1500V isolation channel-to-channel

 Supports J, K, R, S, T, E, and L

thermocouples and millivolt inputs

 Advanced preprocessing with on-board

scaling, alarm detection, filtering and

averaging

 Fast 20 mSec update time

CTI 2557-A 16-Channel RTD Input Module

The Model 2557-A is designed to translate 10 Ohm copper, 100 Ohm

platinum and, 120 Ohm nickel RTDs or millivolt input signals into

scaled digital words which are then sent to the programmable

controller (PLC).

The 2557-A RTD Input Module features built-in independent two,

three, or four lead compensation for each RTD input.

The 2557-A uses 8 8 point removable wiring connectors.

The connectors are provided with the module. Support for other

RTD types is available through special request from the factory.

Call CTI at 1-800-537-8398 to determine if support is available for

your special RTD type.

Features

• Replaces Siemens® 505-2557. CTI 2557

• 16 bit ADC for each channel

• Supports 10Ω copper, 100Ω platinum, and 120Ω nickel RTDs, and

millivolt inputs

• Advanced preprocessing with on-board scaling

• Alarm detection

• Filtering and averaging

• Fast 20 mSec update time

• Open RTD detection and lead resistance compensation

• Support for 2. 3. or 4 wire RTD elements

• Removeable connectors

CTI 2500-OPC Host Name Resolution

Host Name Resolution

KEPServerEX allows for host name resolution which is an alias assigned

to identify a TCP/IP host or its interfaces. Host names are used in all 

TCP/IP environments and user can specify host name instead of an IP

address when using KEPServerEX v5.

OPC UA (Unified Architecture)

KEPServerEX supports OPC UA Client Connections and the OPC DA

data set.

OPC AE (Events)

KEPServerEX exposes event log data (Events) to OPC AE Client

applications. The Event server works in runtime and service modes

supporting 3 Event categories (Information, Warning, Error).

KEPServerEX also supports AE client filtering by event type, severity,

and category and is OPC Compliant.

CTI 2502 2-Channel High Speed Counter Input Module

The 2502 module provides two high-speed 16-bit counter channels

in a compact, single-wide module to fit in the 2500 Series® I/O base.

The CTI 2502 Two-Channel High Speed Counter Input Module is a

member of Control Technology’s family of I/O modules compatible

with CTI 2500 Series™ and Simatic® 505 programmable controllers.

It is designed to count pulses on the inputs and return the current

count and status to the controller.

Features

• Replaces Siemens® 505-7002 with no rewiring

• Two independent high-speed 16-bit counter channels

• Each counter has

• pulse counter mode

• 1X, 2X, 4X quadrature counter modes

• 10 KHz count rate with minimum pulse width of 25us

• two count inputs, two outputs

• reset input and inhibit input

• LED indicators

CTI 2557 16-Channel Isolated RTD Input Module

Description

The 2557 is a high-speed 16-channel RTD input module designed to be

compatible with the CTI 2500 Series or Simatic® 505 I/O base. 

The 2557 translates millivolt level signals from the RTD element into a

scaled temperature value. Multiple RTD types are supported as well as

millivolt inputs. The module performs scaling, alarm detection, filtering,

peak and valley hold, and averaging.

The standard mode logs in as a 16 WX input module. The advanced

mode logs in as 16 X, 16 Y, 32 WX, and 32 WY registers in the PLC.

Features

• Simatic® 505 I/O base format

• 1500 V isolation channel-to-PLC backplane

• 1500 V isolation channel-to-channel

• 16 bit ADC for each channel

• Supports 10Ω Cu, 100Ω Pt, and 120Ω Ni RTDs and millivolt inputs

• Fast 20 mSec update time

• Support for 2. 3. or 4 wire RTD elements

CTI 2502 Two-Channel High Speed Counter Module

The 2502 Two-Channel High Speed Counter Module has two independent

counting channels.  Each channel has four inputs. Each input may be

used as either sinking or sourcing (with external 5–24 VDC power supply).

The input signals are connected to the field wiring terminal block.

Reset – Current flow through the reset input sets the channel’s counter

to zero. The counter will be held at zero until the reset input becomes

inactive.

Inhibit – Current flow through the inhibit input inhibits the channel from

counting. The counter holds at the last value and does not change until

the inhibit input becomes inactive.

Counter Input A, Counter Input B – The relationship of the states of these

two inputs, combined with the counter mode setting, determines the

direction of the count. Typical devices for counting are high-speed static

switches or incremental encoders.

Search for products