Welcome to the official website of CNIACS Automation Technology Co., Ltd!

CTI 2500-C300 CPU with 512K User Memory

The 2500-C300 CPU provides discrete, analog, loop, advanced mathematical,

and high-speed sequential control capability for your CTI 2500 Series® or

Simatic® 505 control system

Features

• Replaces Siemens® 555-1101. 555-1103. 555-1105 with no rewiring

• 512K user memory

• 8192 digital / 8192 analog I/O

• 512 loops / 512 alarms

• Built-in Ethernet for programming and MMI

• Built-in USB for programming

• Profibus-DP master and RS485 Remote I/O ports

• Built-in SD flash card slot for firmware update

CTI 2500-C200 CPU with 256K User Memory

Application Notes

• Capturing Diagnostic Information on CTI 2500 Series CPUs (YouTube Video)

• Redundancy and Backup Solutions (MS-Powerpoint)

• Understanding CIDR Notation Used for IP Address Display on 2500 Series® Processors

• Connecting CTI 2500 Series® Processors to Siemens® COROS® OP/TP HMI Units

using Profibus – Driver Files & Documentation

• Providing Diagnostic Data for Support on CTI 2500 Series® Processors and Coprocessors

• What causes a CPU to go into Fatal Error and how do I recover?

• Adding Serial Ports to 2500 Series® Processors using GridConnect NET232 Adapter

• Configuration of Serial Ports on CTI 2500 Series® and Simatic® 545/555 Processors

• Identifying Hardware Revision Level on 2500 Series® Processors

• Accessing Memory Above 1856K on 2500-C400 Processors using APT®

• Optimizing Performance Using the 2500 Series® Processor

• Connecting to a 2500 Series® Processors using PLC Workshop

• 2500 Series® Redundancy Options

• Guide to Upgrading TI560/565 to CTI 2500 Series® System

• Guide to Upgrading TI520C& 530T to CTI 2500 Series® System

• Recovering the Event Log from a CTI 2500 Series® Processor

• 2500 Series Processor V6.02 Firmware Enhancements

• Using the Port Lockout Feature on 2500 Series® Processor to prevent simultaneous program edits

• PID Loop Bumpless Transfer with CTI and Simatic/TI PLCs

• Setting Up S7-1500 as a Profibus-DP Slave on CTI 2500 Series® Processors- Sample Files

• CPU Redundancy with 2541 and 2500P-ACP1/JACP (sample program files for CPU, 2541. ACP1/JACP)

• Setting Up S7-1500 as a Profibus-DP Slave on CTI 2500 Series® Processors

• CPU Redundancy with 2541 and 2500P-ACP1/JACP (pdf application note)

• E89 Error on 2500-Cxxx Family Processors

• Recovering Diagnostic Data from a CTI 2500 Series® Processor

CTI 2500-C200 CPU provides discrete, analog, loop, advanced mathematical

The 2500-C200 CPU provides discrete, analog, loop, advanced mathematical,

and high-speed sequential control capability for your CTI 2500 Series® or

Simatic® 505 control system

Features

• Replaces Siemens® 545-1101. 545-1102. 545-1104. 545-1106 with no rewiring

• 256K user memory

• 2048 digital / 1024 analog I/O

• 64 loops / 128 alarms

• Built-in Ethernet for programming and MMI

• Built-in USB for programming

• Profibus-DP master and RS485 Remote I/O ports

• Built-in SD flash card slot forfirmware update

CTI 2500-C100 Application Notes

Application Notes

• Capturing Diagnostic Information on CTI 2500 Series CPUs (YouTube Video)

• Redundancy and Backup Solutions (MS-Powerpoint)

• Understanding CIDR Notation Used for IP Address Display on 2500 Series®

Processors

• Connecting CTI 2500 Series® Processors to Siemens® COROS® OP/TP HMI

Units using Profibus – Driver Files & Documentation

• Providing Diagnostic Data for Support on CTI 2500 Series® Processors and

Coprocessors

• What causes a CPU to go into Fatal Error and how do I recover?

• Adding Serial Ports to 2500 Series® Processors using GridConnect NET232 Adapter

• Configuration of Serial Ports on CTI 2500 Series® and Simatic® 545/555 Processors

• Identifying Hardware Revision Level on 2500 Series® Processors

• Accessing Memory Above 1856K on 2500-C400 Processors using APT®

• Optimizing Performance Using the 2500 Series® Processor

• Connecting to a 2500 Series® Processors using PLC Workshop

• 2500 Series® Redundancy Options

• Guide to Upgrading TI560/565 to CTI 2500 Series® System

• Guide to Upgrading TI520C& 530T to CTI 2500 Series® System

• Recovering the Event Log from a CTI 2500 Series® Processor

• 2500 Series Processor V6.02 Firmware Enhancements

• Using the Port Lockout Feature on 2500 Series® Processor to prevent simultaneous

program edits

• CPU Redundancy with 2541 and 2500P-ACP1/JACP (pdf application note)

• Setting Up S7-1500 as a Profibus-DP Slave on CTI 2500 Series® Processors

• CPU Redundancy with 2541 and 2500P-ACP1/JACP (sample program files for CPU,

2541. ACP1/JACP)

• Setting Up S7-1500 as a Profibus-DP Slave on CTI 2500 Series® Processors- Sample

Files

• Recovering Diagnostic Data from a CTI 2500 Series® Processor

• E89 Error on 2500-Cxxx Family Processors

• PID Loop Bumpless Transfer with CTI and Simatic/TI PLCs

CTI 2500-C100 CPU with 128K User Memory

The 2500-C100 CPU provides discrete, analog, loop, advanced mathematical

and high-speed sequential control capability for your CTI 2500 Series® or

Simatic® 505 control system.

Features

• Replaces Siemens® 545-1103 and 545-1105 with no rewiring

• Note that if the Siemens® processor includes a Profibus-DP annex card,

then 2500-C200 must be used

• 128K user memory

• 1024 digital / 1024 analog I/O

• 16 loops / 32 alarms

• Built-in Ethernet for programming and MMI

• Built-in USB for programming

• Built-in SD flash card slot for firmware update

CTI 2553-A 2-Channel Isolated Mag Meter Input Module

Description

The 2553-A 2-Channel Mag Meter Input Module rapidly measures the frequency

of a magnetic pulse tachometer with high resolution. It is designed to be compatible

with the CTI 2500 SeriesTM or Simatic® 505 I/O base in local, remote I/O,

and Profibus configurations.

Fast update time and high accuracy across the full frequency specification make the

2553-A ideal for gas turbine speed mea- surement applications.

Features

• Reflex counter

• N-tooth mode counting

• 1500 VDC isolation channel-to-channel

• 1500 VDC isolation channel-to-backplane

• Reports measurement in frequency or period

Specifications

Channels: 2 Isolated Mag Meter Inputs

Input Voltage Range: 140 mV to 50 VRMS (differential input into 10 KΩ)

200 mV to 70 V Peak

Input Frequency Range: 78 Hz to 65 KHz

Frequency Roll-Off : 3 dB at 20 KHz

6 dB per octave

Input Protection: 50 VRMS continuous 20.000 Volts ESD

Digital Filtering: User-selectable (50 mS Time Constant)

Update Time: 7 mSec for all channels

Accuracy: ±1 Hz

Isolation: 1500 VDC channel-to-channel

1500 VDC channel-to-PLC

Connector: Removable

Wire Gauge: 12 -26 AWG

Backplane Power: 2.5 Watts @ +5 VDC

Module Size: Single-wide

Shipping Weight: 1.5 lbs (0.68 Kg)

Additional Product Information:

On CTI’s Website you find will links to the 2500 Series Std Environmental Specifications

and the UL Agency Certificates of Compliance .

CTI 2559-TC 8-Channel Thermocouple Input Module

Description

The 2559-TC is a high-speed 8-point thermocouple

input module designed to translate

millivolt level signals from the thermocouple

element into a scaled temperature value in a CTI

2500 Series or Simatic® 505 I/O base.

Features

• CTI 2500 Series or Simatic® 505 base format

• Replaces Siemens® 505-7028 with no rewiring

• 1500V channel-to-PLC backplane isolation

• Fast 9 mSec update time all channels

• Microprocessor self-diagnostics

• Supports J, K, T, E, R, S, & N thermocouples and millivolt inputs

• No CJC calibration needed

CTI 2559-TC Specifications

Specifications

Inputs per module: 8

Thermocouple types: J, K, T, E, R, S, N, and mV

Isolation: 1500 VDC channel-to-backplane

Input overrange protection:

30 VDC or VAC continuous

120 VAC for 10 Sec

Measurement ranges:

J: -210oC to 760oC (-350oF to 1400oF)

K: -270oC to 1372oC (-450oF to 2500oF)

T: -270oC to 400oC (-454oF to 752oF)

E: -270oC to 1000oC (-454oF to 1832oF)

R: 0oC to 1768oC (32oF to 3214oF)

S: 0oC to 1768oC (32oF to 3214oF)

N: -260oC to 1300oC (-436oF to 2372oF)

mV: -55 to +55mV

Millivolt input impedance:

4.4MΩ DC, >10KΩ @60 Hz

Open Thermocouple Detect: less than 1 Sec

Data presentation:

With scaling enabled = 0 – 32000 (temp.)

-32000 to +32000 (mV)

With scaling disabled = oC or oF x10 (temp.)

-10000 to +10000 (mV)

Measurement units: Degrees C or F

selectable by module

Digital Filtering Time Constant: 80 mSec

Update time:

9 mSec all channels

Repeatability: +/-1oC, +/-2oF for all

thermocouple types

Accuracy: Types

J: +/-1oC from 0oC to 60oC

K: +/-1oC from 0oC to 60oC

T: +/-1oC from 0oC to 60oC

E: +/-1oC from 0oC to 60oC

R: +/-2oC from 0oC to 60oC*

S: +/-2oC from 0oC to 60oC*

N: +/-1oC from 0oC to 60oC

mV: +/-0.5% full scale or +/- 500μV

ADC Resolution: 16 bits

Common Mode Rejection: >110 db @ 60 Hz

Normal Mode Rejection:

>60 db @ 60 Hz, >50 db @ 50 Hz

Connector: Removable

Wire Gauge: 14-22 AWG

Backplane Power: 1.0 Watt (maximum)

Module Size: Single-wide

Operating Temperature: 0o to 60oC (32o to 140oF)

Storage Temperature: -40o to 85oC (-40o to 185oF)

Relative Humidity: 5% to 95% (non-condensing)

Agency Approvals Pending:

UL, ULC, Class 1-Div. 2. CE

Shipping Weight: 1.5 lb. (0.68 Kg)

CTI 2552-A Specifications

Specifications

Input Channels: 8 RTD input channel, independently isolated and configurable

RTD Types:

ΩTCR = 0.003850. Ω/Ω/°C

European DIN 43760

-198 °C to 849.8 °C (-327.6°F to 1561.6°F)

Ω TCR = 0.00672. Ω/Ω/oC

Temperature Range: -79.8°C to 260.0°C (-111.6°F to 500.0°F)

Other RTD types by special request: 0Ω Cu

Absolute Temp Accuracy: +0.4°C (+0.8°F)

Millivolt Range: 0 to 103.04 Millivolts

Millivolt Input Impedance: >10KΩ @ 60Hz

Absolute Millivolt Accuracy: +0.5% full scale or +500μV

Lead Compensation: 20Ω per lead wire

Bias Current to RTD Probe: 250 microamps

Digital Filtering Time Constant: 0.3 Sec

Output Units: Degrees C or F

Repeatability: 0.05% full scale

Resolution: 0.025% full scale

Update Time: 2msec per channel

Common Mode Rejection: >110db @ 60Hz (digital filtering disabled)

Normal Mode Rejection: >145db @ 60Hz (digital filtering enabled)

Input ESD Protection: 20.000V

Overrange Protection: 20 VDC input to common

Isolation: 1500V channel-to-channel

1500 VDC channel-to-PLC

Connector: Fixed 32 position terminal strip

Wire Gauge: 18-24 AWG

Backplane Power: 2.75W @ 5 VDC

Module Size: Single-wide

Shipping Weight: 1.5 lb. (0.68 Kg)

CTI 2552-A 8-Channel Isolated RTD Input Module

Description

The2552-A is a high-speed 8-channel isolated RTD input module designed to be

compatible with the CTI 2500 Series® or Simatic® 505 I/O base in local, remote I/O,

and Profibus configurations. The 2552-A translates RTD input signals into a scaled

temperature value.

Features

CTI 2500 Series® or Simatic® 505 base format

1500V channel-to-channel isolation

1500V channel-to-PLC backplane isolation

Fast 2msec update time per channel

Detects open in RTD or field wiring

Compensates for lead wire resistance

Supports 0 – 100 millivolt inputs on anychannel

Additional Product Information:

On CTI’s Website you will find links to the 2500 Series Standard Environmental Specifications

and the UL Agency Certificates of Compliance.

Search for products

Back to Top
Product has been added to your cart