Specifications
Outputs per Module: 8.16. or 32
Isolation: 2100 VDC channel-to-backplane
3000 VDC group-to-group
Output Voltage: 11 VDC to 125 VDC
Output Source Current per Circuit:
2.0 Amps max., 1 mA min.
Total Module Output Current: 32 Amps max.
from 0o to 60oC
Maximum Surge Current: 3 Amps for 15 Sec
“ON” State Voltage Drop: 0.5V @ 1.0 Amp
“OFF” State Leakage Current: <20µA
Turn On Time: 1 mSec (nominal)
Turn Off Time: 3 mSec (nominal)
Fuses: 32. 2.5 amp, 250V,
Type: Littlefuse #21602.5.
Bussman GDA-2.5 (Field replaceable)
Connector: Removable
Wire Gauge: 14 – 22 AWG
Backplane Power: 1.7 Watts max.
Module Size: Single-wide
Operating Temperature: 0o to 60oC
(32o to 140oF)
Storage Temperature: -40o to 85oC
(-40o to 185oF)
Relative Humidity: 5% to 95%
(non-condensing)
Agency Approvals Pending:
UL, ULC, FM (Class 1. Div.2), CE
Shipping Weight: 1.5 lb. (0.68 Kg)
Leave a comment