Specifications
Outputs per Module: 8
Isolation:
2100 VDC channel-to-backplane
3000 VDC group-to-group
Output Voltage: 11 VAC to 240 VAC
Maximum Output Current:
2.0 Amps max.,
4A per group
16A per module
For Class 1 Div 2 locations:
2A per point @50°C
1.5A per point @ 60°C
Maximum Surge Current: 3 Amps for 15 Sec
“ON” State Voltage Drop: 1.0V @ 1.0 Amp
“OFF” State Leakage Current: 1mA
Turn On Time: 1 AC cycle
Turn Off Time: 1 AC cycle
Fuses:
16. 2.5 amp, 250V, Type: Littlefuse #21602.5.
Bussman GDA-2.5 (Field replaceable)
Connector: Removable Part# 2500-40F
Note: The connector is ordered separately.
Wire Gauge: 14 – 22 AWG
Backplane Power: 1.25 Watts max.
Module Size: Single-wide
Shipping Weight: 1.5 lb. (0.68 Kg)