Specifications
Input Channels: 8 isolated input channels, individually configurable for thermocouple or millivolt input
Thermocouple Types: J or K, jumper selectable for each channel
Millivolt Input: 0 – 55 mV
Digital Filtering Time Constant: 0.3 Sec
Output Units: Degrees C or F,
(jumper selectable for all outputs)
Repeatability: 0.05%
Accuracy: Type J: ±1° from 0° to 760°C
Type K: ±1° from 0° to 1372°C Millivolt: .06 Millivolt
Resolution: 0.3°C, 0.6°F thermocouple input
.020 millivolt input
Common Mode Rejection:
>110db @ 60Hz (digital filtering disabled)
Normal Mode Rejection:
>45db @ 60Hz (digital filtering enabled)
Input ESD Protection: 20.000 V
Overrange Protection: 20 VAC for 1 minute (all input terminals)
Isolation: 1500 VDC channel-to-channel 1500 VDC channel-to-PLC
Connector: Fixed
Wire Gauge: 18-24 AWG
Backplane Power: 2.4 Watts
Module Size: Single-wide
Shipping Weight: 1.5 lb (0.68 Kg)