Safety Function
The module does not perform any safety-related functions.The module evaluates
the input signals of proximity switches and contact makers andmonitors the
proximity switch / contact maker circuit for open-circuits and short-circuits.
The parameters and status for this module must not be used for safety functions.
Reaction in the Event of a Fault
If a fault occurs, the assigned input variables transmit the initial value (default
value = 0) tothe user program.The initial values must be set to 0 to ensure that
the input variables transmit the value 0 tothe user program if a fault occurs.
If the raw value is evaluated instead of the processvalue, the user must program
the monitoring function and the value in the event of faultsfrom within the user
program.The module activates the Error LED on the front plate.
Scope of Delivery
The module must be installed on a suitable connector board to be able to operate.
If a FTAis used, a system cable is required to connect the connector board to the FTA.
Connectorboards, system cables and FTAs are not included within the scope of delivery.
The connector boards are described in Chapter 3.6. the system cables are described in
Chapter 3.7. The FTAs are described in own manuals.