Safety Function

The module does not perform any safety-related functions.The module evaluates

 the input signals of proximity switches and contact makers andmonitors the

proximity switch / contact maker circuit for open-circuits and short-circuits.

The parameters and status for this module must not be used for safety functions.

Reaction in the Event of a Fault

If a fault occurs, the assigned input variables transmit the initial value (default

value = 0) tothe user program.The initial values must be set to 0 to ensure that

the input variables transmit the value 0 tothe user program if a fault occurs.

If the raw value is evaluated instead of the processvalue, the user must program

the monitoring function and the value in the event of faultsfrom within the user

program.The module activates the Error LED on the front plate.

Scope of Delivery

The module must be installed on a suitable connector board to be able to operate.

If a FTAis used, a system cable is required to connect the connector board to the FTA.

Connectorboards, system cables and FTAs are not included within the scope of delivery.

The connector boards are described in Chapter 3.6. the system cables are described in

Chapter 3.7. The FTAs are described in own manuals.