Load Current Approaches Fault Current
Pickup settings on a phase overcurrent device are normally set below the expected fault current levels on
that line by some margin. Consequently, it is possible for load current to approach (or exceed) the pickup
setting on the relay. This could lead to an undesirable trip for an acceptable load condition.
Weak Infeed Condition
During a period of abnormally low system voltage, leading power factor current above relay pickup can
flow in the non-trip direction of a line. Probable current sources are outlying capacitor banks. This could
cause the current to be sensed as lagging current flowing in the trip direction and leading to an
undesirable trip. (A condition often referred to as weak infeed because the lower voltage system – where
load is present – attempts to correct the undervoltage condition on the higher voltage system.)