CALIBRATION
The calibration marks on the faceplate have a maximum
error of 10% and are provided only as guides. Proper
calibration requires using an accurate voltmeter in parallel
with the input signal. Use the following procedure to
calibrate your relay.
Unbalance
1. Adjust the UNBAL control fully clockwise and the
DELAY control fully counterclockwise.
2. Apply three-phase, nominal input voltage with the
proper phase sequence to the relay. The output relay
should energize.
3. Lower one phase of the applied voltage to the desired
trip level. Slowly adjust the UNBAL control
counterclockwise until the relay trips.
Delay
1. Set the DELAY control at the desired time setting.
2. Apply three-phase, nominal input voltage with the
proper phase sequence to the relay.