Settings Example
A BE3-47N/27 relay with a nominal input rating of 120 Vac
has the following settings:
• UNBAL – 10%
• DELAY – 5 s
The relay detects a phase unbalance when any one phase
decreases to 108 Vac or increases to 132 Vac. The output
relay trips five seconds after the phase unbalance is
detected. The output relay also trips if all phases decrease
to 85% of nominal, or 102 Vac.
INSTALLATION
BE3 phase balance relays are designed for mounting on
standard DIN rails that comply to DIN-EN 50022. Mounting
involves hooking the top edge of the cutout on the base of
the case over one edge of the DIN rail. The opposite side of
the cutout containing the release clip is then pushed over
the opposite side of the DIN rail. To remove or reposition the
relay, lever the release clip and move the relay as required.
BE3 relays should be installed in a dry, vibration-free
location where the ambient temperature does not exceed
the operating temperature range. Connections to the relay
should be made using wire that meets applicable codes and
is properly sized for the application. Figure 1 shows the
terminal connections for the BE3-47N/27 relay. Connections
for the BE3-47N relay are identical.