The BE1-32R Directional Overpower Relay and the BE1-32O/U Directional
Over/Underpower Relay are solid-state devices which provide versatility
and control in protecting machines against reverse power flow,
underpower and overpower conditions.
ADVANTAGES
Measures Real Power – El cos Θ.
Wide variety of input configurations are available including single-phase
and three phase, 3 and 4 wire systems.
Sensing ranges available from 0.5 to 6000 watts secondary.
Instantaneous, definite and inverse timing characteristics available.
Low input sensing and supply burdens.
Qualified to the requirements of
IEEE C37.90.1-1989 and IEC 255 for fast transient and surge
withstand capability;
IEC 255-5 for impulse.
UL recognized under Standard 508. UL File #E97033.
Five year warranty.
The BE1-32R Directional Overpower Relay and the BE1
32 O/U, Directional Over/Underpower Relays sense real
power flow (El cos Θ). These relays are solid-state
devices designed for use in single-phase or three-phase
systems to provide equipment protection for overpower
and/or underpower or to be used for supervisory control
of circuits. Both relay configurations may be used to
monitor either forward or reverse power. In the following
application examples, single-phase connections are
shown for simplicity.