APPLICATION EXAMPLES
The BE1-32 relays (R and O/U) are typically used in
applications where excessive power flow in the tripping
direction is indicative of undesirable situations. Typical
examples are discussed below. Notice: This product is
not recommended for power factors below 0.10. Contact
Basler Electric for recommended products.
EXAMPLE 1 – ANTI MOTORING
In this example, the power relay is used to protect the
prime mover rather than the generator. When an ac
generator, operating in parallel with a power system,
loses prime mover torque, it remains in synchronism
with the system and continues to run as a synchronous
motor drawing sufficient power from the system to drive
the prime mover. Sustained motoring can cause severe
damage to the prime mover. The Directional Power
Relay, with its wide sensitivity range, can detect levels of
reverse real power flow as low as 0.5 Watts secondary
and provide an alarm or trip the unit off line (See Figure
1). In this example, single phase sensing is usually
considered sufficient, since motoring is a balanced
condition.