APPLICATION:
The BE3-25 series are synchronizing check relays, also known
as paralleling relays. They are used to ensure that two AC
supplies are synchronized. For a system to be synchronized,
the frequency, phase angle, and voltage must be within preset
limits. The BE3-25-****4 can monitor either utility mains bus
bar and incoming generator, or two generators.
The BE3-25-****4 offers user adjustment of the reset voltage
from 10 to 30%. This voltage corresponds to 6 to 20 electrical
degrees. The unit compares the input voltage and phase
relationship of the bus bar to that of the generator.
When the signal is within the preset limits, the relay energizes.
The BE3-25-****5 operates as the BE3 25-****4.
but has the additional feature of a dead bus facility.
This enables the relay to energize with a generator supply
only, which is a common requirement when utility mains failure
occurs.