DECS-450 Models
Part number 9372900104 identifies the FIT
assembly. Part Number 9372900105 identifies the
FIT packaged for shipping and should be specified
when requesting a replacement or spare module.
Each FIT is supplied with a cable (Part number:
9372900021) for connecting the FIT (connector J1) to
the DECS.
For EMC-compliant installations, use FIT
9372900104 or 9372900105. and Cable 9372900021
with the DECS-450.
FUNCTIONAL DESCRIPTION
Field sensing current is supplied to the module by a
user-supplied current shunt with an output rating of
50 mVdc or 100 mVdc. The field current sensing
input accepts up to 300% of the nominal current
range. The field current signal is converted into a
voltage signal from 2 to 9.5 Vdc and sent to the
DECS through connector J1.
Field sensing voltage is supplied directly from the
field to the module. The FIT accepts one of five field
voltage ranges: 63 Vdc, 125 Vdc, 250 Vdc, 375 Vdc,
or 625 Vdc. The field voltage sensing input accepts
up to 300% of the nominal voltage range. The field
voltage signal is low-pass filtered, converted into a
voltage signal from 0.9 to 9.1 Vdc, and sent to the
DECS through connector J1.