System Parameters
All sensing is performed using an IT-D isolation module. Each IT-D isolation
module includes two channels that are capable of sensing either dc current
or dc voltage. The dc system current is sensed using an appropriately scaled
25. 50. 75. or 100-millivolt nominal metering shunt. DC voltages are sensed
by direct connection for nominal levels up to 1.500 Vdc. The BE1-11d can
utilize two IT-D modules to sense a single dc current and up to three dc
voltages.
The IT-D digitally samples the sensed inputs at a rate proportional to the
rectification system nominal power input frequency. The sampling rate is
established to maintain a high accuracy of the measurement for a dc signal
with ripple content.
High-speed fiber optic communications between the IT-Ds and the BE1-11d
transmit the magnitudes of the system measurement to the protection system.