DESCRIPTION

BE1-87T Transformer Differential Relays provide primary protection for power transformers and are

available in either Single-Phase or Three-Phase configurations. The solid-state BE1-87T compares the

currents entering and leaving the protected transformer. If a fault is detected, the relay initiates a trip

signal to isolate the power transformer. This limits damage to the transformer and minimizes the impact

on the power system.

BE1-87T relays use three types of restraint:

• Percentage of through-current

• Second harmonic

• Fifth harmonic

Selectivity in differential relaying is based on the ability to distinguish between internal and external faults.

This is achieved by comparing the currents into and out of a power transformer. Comparing these

currents often requires more than two inputs. For example:

• Power transformers may have a significant portion (greater than 10 %) of the current flowing in a

third or tertiary winding.

• Power transformers can have multiple breakers for a given winding (e.g., ring bus or breaker

and-a-half bus).

BE1-87T relays are available with up to five restraint inputs for the single-phase unit and up to three

restraint inputs per phase for the three-phase unit.