DESCRIPTION
BE1-87T Transformer Differential Relays provide primary protection for power transformers and are
available in either Single-Phase or Three-Phase configurations. The solid-state BE1-87T compares the
currents entering and leaving the protected transformer. If a fault is detected, the relay initiates a trip
signal to isolate the power transformer. This limits damage to the transformer and minimizes the impact
on the power system.
BE1-87T relays use three types of restraint:
• Percentage of through-current
• Second harmonic
• Fifth harmonic
Selectivity in differential relaying is based on the ability to distinguish between internal and external faults.
This is achieved by comparing the currents into and out of a power transformer. Comparing these
currents often requires more than two inputs. For example:
• Power transformers may have a significant portion (greater than 10 %) of the current flowing in a
third or tertiary winding.
• Power transformers can have multiple breakers for a given winding (e.g., ring bus or breaker
and-a-half bus).
BE1-87T relays are available with up to five restraint inputs for the single-phase unit and up to three
restraint inputs per phase for the three-phase unit.